HML/PSE PHOTOELECTRIC SMOKE DETECTOR

FEATURES

  • Low profile design
  • Low current draw
  • Backward compatible with Series 100 detector range of bases
  • Wide operating voltage 8 to 30VDC
  • Bi-colour LED detector status indicator
  • Automatic drift compensation
  • Programmable sensitivity
  • Addressable feature
  • Advanced maintenance features via remote hand-held test unit
  • Range of detector bases available
Product Enquiry
Category:

The HML/PSE photoelectric smoke detector forms part of the EWit Morley Lite range of addressable detectors. This range of detectors has been produced using the latest in manufacturing and design techniques, pushing out the boundaries of existing detector technology.

The HML/PSE photoelectric detector incorporates an Application Specific Integrated Circuit (ASIC). Combined with the latest state of the art optical chamber the detector provides efficient and accurate detection of fires with a high level of resilience to non-fire environmental influences.

The HML/PSE detector is backward compatible with the Series 100 detector bases, thus providing the capability to upgrade, extend and maintain existing Series 100 installations.

The HML/PSE detector incorporates a bi-colour LED indicator. The integral LED changes colour according to the detector’s status – Green = Normal, Red = Alarm. This benefits the user by providing clear, instant visual indication of the detector’s condition. The Green LED can be programmed for blink/no blink operation.

‘Drift compensation’ algorithms are one of the key features of the HML/PSE detector. These algorithms ensure a consistent alarm sensitivity threshold for periods between service intervals. This provides the user with both a reduction in the frequency of nuisance alarms and maintenance savings by extending the period before cleaning of the detector chamber is required.

The sensitivity of a smoke detector is critical to its overall performance, this is reflected in both its ability to detect real fire conditions and its resilience to non-fire stimuli. The HML/PSE’s performance can be optimised for it’s application by selecting from one of three preset alarm thresholds – Low, Medium and High, offering greater stability and optimum performance within the environment in which it has been installed. The selection is easily achieved through the use of a remote hand-held tool.

The remote hand-held programming unit can also be used to gain access to other advanced features. The features available include: read/write last maintenance date, read chamber contamination level, read value of thermal element and perform an alarm test.

HML/PSE ARCHITECT/ENGINEER SPECIFICATIONS

 HML/PSE PHOTOELECTRIC SMOKE DETECTOR

Each unit can be given a unique address that will be displayed on the Morley Lite fire alarm control panel whenever the detector is in alarm. All the features via the hand-held programming unit are achieved effectively and effortlessly without the need to remove the detector or having to gain direct physical access (other than by the use of ‘No Climb Products’ or similar servicing tool), saving valuable commissioning/maintenance time.

They provide the end user with the confidence to know that his system is being regularly serviced and that it is operating at its optimum level, with minimum disruption to his own business activities.

ELECTRICAL SPECIFICATIONS
Operating Voltage Range 8 to 30VDC (Nominal 12/24VDC)
Typical Standby Current @ 25ÞC 50µA @ 24VDC (LED no blink)
Maximum Alarm Current (LED On) 80mA @ 24VDC (Limited by panel)
ENVIRONMENTAL SPECIFICATIONS
Application Temperature Range -30⁰C to +70⁰C
Humidity 5 to 95% Relative Humidity (non condensing)
MECHANICAL INFORMATION
Height 38mm (plus 9mm for B401 base)
Diameter 102mm
Weight 105g (plus 60g for B401 base)
Max Wire Gauge for Terminals 0.75mm2 to 2.5mm2
Colour Pantone Warm Grey 1C
Material Bayblend FR110

In addition to the comprehensive programming tool, a simple laser based alarm test unit is also available. The coded signal transmitted by this device can instruct the detector to generate a full alarm condition at a range of up to 5 metres from the detector, and is an ideal tool for initial commissioning and routine system testing.

A variety of detector bases can be used with the HML/PSE detector, providing application flexibility and compatibility with a wide range of Fire Alarm Control Panels. All bases are fitted with a shorting spring to permit circuit testing prior to fitting the detector and have a tamper resistant feature, which when activated prevents removal of the detector without the use of a tool.

All Morley Lite products are covered by standard 1 year warranty.

PRODUCT RANGE

COMPATIBLE BASES (see notes)
B401 Standard Base
B401R Resistor base with 470 ohm resistor
B401RSD Standard base with 470 ohm resistor and Shottky diode
B401RM Standard recess base with 470 ohm resistor
B401DGR Deep base with 470 ohm resistor
B312NL 12V non-latching relay base
B324RL 24V latching relay base
B312RL 12V latching relay base
B401DGSD Deep base with Shottky diode
B401SD Standard base with schotty diode
B401DG Deep base
ACCESSORIES
S300RPTU Remote Programming and Test Unit S300RTU Remote Test Unit
S300SAT Remote Programming Interface Unit S300ZDU Zonal Display Unit
Other HML Detectors HML/PTSE, HML/RHSE

Notes: Bases with other resistor values are available to suit the requirements of most Fire Alarm Control Panels.

Reviews

There are no reviews yet.

Only logged in customers who have purchased this product may leave a review.