The HML/PSE photoelectric smoke detector forms part of the EWit Morley Lite range of addressable detectors. This range of detectors has been produced using the latest in manufacturing and design techniques, pushing out the boundaries of existing detector technology.
The HML/PSE photoelectric detector incorporates an Application Specific Integrated Circuit (ASIC). Combined with the latest state of the art optical chamber the detector provides efficient and accurate detection of fires with a high level of resilience to non-fire environmental influences.
The HML/PSE detector is backward compatible with the Series 100 detector bases, thus providing the capability to upgrade, extend and maintain existing Series 100 installations.
The HML/PSE detector incorporates a bi-colour LED indicator. The integral LED changes colour according to the detector’s status – Green = Normal, Red = Alarm. This benefits the user by providing clear, instant visual indication of the detector’s condition. The Green LED can be programmed for blink/no blink operation.
‘Drift compensation’ algorithms are one of the key features of the HML/PSE detector. These algorithms ensure a consistent alarm sensitivity threshold for periods between service intervals. This provides the user with both a reduction in the frequency of nuisance alarms and maintenance savings by extending the period before cleaning of the detector chamber is required.
The sensitivity of a smoke detector is critical to its overall performance, this is reflected in both its ability to detect real fire conditions and its resilience to non-fire stimuli. The HML/PSE’s performance can be optimised for it’s application by selecting from one of three preset alarm thresholds – Low, Medium and High, offering greater stability and optimum performance within the environment in which it has been installed. The selection is easily achieved through the use of a remote hand-held tool.
The remote hand-held programming unit can also be used to gain access to other advanced features. The features available include: read/write last maintenance date, read chamber contamination level, read value of thermal element and perform an alarm test.
HML/PSE ARCHITECT/ENGINEER SPECIFICATIONS
HML/PSE PHOTOELECTRIC SMOKE DETECTOR
Each unit can be given a unique address that will be displayed on the Morley Lite fire alarm control panel whenever the detector is in alarm. All the features via the hand-held programming unit are achieved effectively and effortlessly without the need to remove the detector or having to gain direct physical access (other than by the use of ‘No Climb Products’ or similar servicing tool), saving valuable commissioning/maintenance time.
They provide the end user with the confidence to know that his system is being regularly serviced and that it is operating at its optimum level, with minimum disruption to his own business activities.
ELECTRICAL SPECIFICATIONS | |
---|---|
Operating Voltage Range | 8 to 30VDC (Nominal 12/24VDC) |
Typical Standby Current @ 25ÞC | 50µA @ 24VDC (LED no blink) |
Maximum Alarm Current (LED On) | 80mA @ 24VDC (Limited by panel) |
ENVIRONMENTAL SPECIFICATIONS | |
---|---|
Application Temperature Range | -30⁰C to +70⁰C |
Humidity | 5 to 95% Relative Humidity (non condensing) |
MECHANICAL INFORMATION | |
---|---|
Height | 38mm (plus 9mm for B401 base) |
Diameter | 102mm |
Weight | 105g (plus 60g for B401 base) |
Max Wire Gauge for Terminals | 0.75mm2 to 2.5mm2 |
Colour | Pantone Warm Grey 1C |
Material | Bayblend FR110 |
In addition to the comprehensive programming tool, a simple laser based alarm test unit is also available. The coded signal transmitted by this device can instruct the detector to generate a full alarm condition at a range of up to 5 metres from the detector, and is an ideal tool for initial commissioning and routine system testing.
A variety of detector bases can be used with the HML/PSE detector, providing application flexibility and compatibility with a wide range of Fire Alarm Control Panels. All bases are fitted with a shorting spring to permit circuit testing prior to fitting the detector and have a tamper resistant feature, which when activated prevents removal of the detector without the use of a tool.
All Morley Lite products are covered by standard 1 year warranty.
PRODUCT RANGE
COMPATIBLE BASES (see notes) | |
---|---|
B401 Standard Base | |
B401R Resistor base with 470 ohm resistor | |
B401RSD Standard base with 470 ohm resistor and Shottky diode | |
B401RM Standard recess base with 470 ohm resistor | |
B401DGR Deep base with 470 ohm resistor | |
B312NL 12V non-latching relay base | |
B324RL 24V latching relay base | |
B312RL 12V latching relay base | |
B401DGSD Deep base with Shottky diode | |
B401SD Standard base with schotty diode | |
B401DG Deep base | |
ACCESSORIES | |
S300RPTU Remote Programming and Test Unit | S300RTU Remote Test Unit |
S300SAT Remote Programming Interface Unit | S300ZDU Zonal Display Unit |
Other HML Detectors | HML/PTSE, HML/RHSE |
Notes: Bases with other resistor values are available to suit the requirements of most Fire Alarm Control Panels.
Reviews